Cooper Bussmann BRICK 6125TD User Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
Description
• Surface mount fuse, fast acting
• Designed to IEC 127-4
• Surface Mount
• Solder Immersion Compatible
• Overcurrent protection of systems up to 250 VAC
Approvals
Designed to IEC 127, Sheet 4 (approval pending)
Environmental Data
•Termination Strength: IEC 127-4 Clause 8.3.2
Soldered Joints: IEC 127-1 Clause 8.5
Solderability: IEC 127-4 Clause 8.6.2
Resistance to Soldering Heat: IEC 127-4 Clause 8.7
Insulation Resistance: IEC 127-4 Clause 9.3.3
Soldering Method
Wave Immersion: 260°C, 10 sec max.
• Infrared:260°C, 30 sec max.
Ordering
• Specify product code and packaging code
2.77 ± 0.15
(0.109 ± 0.006)
2.77 ± 0.15
(0.109 ± 0.006)
3.07 ± 0.15
(0.121 ± 0.006)
3.07 ± 0.15
(0.121 ± 0.006)
4.38
(0.172)
3.30
(0.130)
6.79
(0.267)
2.77 ± 0.15
(0.109 ± 0.006)
10.29 ± 0.20
(0.405 ± 0.008)
1.4 ± 0.25
(0.055 ± 0.010)
1.4 ± 0.25
(0.055 ± 0.010)
3.07 ± 0.15
(0.121 ± 0.006)
Land Pattern
Dimensions
mm
(inches)
Drawing Not to Scale
Top View
Side View
End View
Brick
Fuses 1025F Series
Fast Acting, Low Breaking Capacity
ELECTRICAL CHARACTERISTICS
% of Amp Rating Opening Time
125% 1 Hour Minimum
200% 2 Minutes Maximum
1000% 0.001 - 0.01 Seconds
SPECIFICATIONS
Voltage Interrupting DC Cold Typical Typical Marking
Product Code Rating Rating* Resistance** (ohms) Melting Voltage Code
AC DC 250VAC 125VDC min. typ. max. I
2
t† Drop‡
1025F250mA 250V 125V 100A 50A TBD TBD TBD TBD TBD D f
1025F500mA 250V 125V 100A 50A TBD TBD TBD TBD TBD F f
1025F800mA 250V 125V 100A 50A TBD TBD TBD TBD TBD KK f
1025F1A 250V 125V 100A 50A TBD TBD TBD TBD TBD H f
1025F1.6A 250V 125V 100A 50A TBD TBD TBD TBD TBD MM f
1025F2A 250V 125V 100A 50A TBD TBD TBD TBD TBD N f
1025F2.5A 250V 125V 100A 50A TBD TBD TBD TBD TBD O f
1025F3.15A 250V 125V 100A 50A TBD TBD TBD TBD TBD Q f
1025F4A 250V 125V 100A 50A TBD TBD TBD TBD TBD S f
1025F5A 250V 125V 100A 50A TBD TBD TBD TBD TBD T f
1025F6.3A 250V 125V 100A 50A TBD TBD TBD TBD TBD OO f
*AC Interrupting Rating (Measured at designated voltage, greater than 95% power factor); DC Interrupting Rating (Measured at designated voltage,
time constant of the calibrated circuit is less than 1 millisecond, battery source)
** DC Cold Resistance (Measured at 10% of rated current)
†Typical Melting I
2
t (Measured with a battery bank at 10x-rated current, not to exceed IR,
time constant of calibrated circuit less than 50 microseconds)
‡Typical Voltage Drop (Measured at rated current after temperature stabilizes)
• Device designed to carry rated current for four hours minimum. An operating current of 80% or less of rated current is recommended, with
further derating required at elevated ambient temperatures.