8-29-01
XXXXXX
Bussmann
®
Power Module
Switch PS
All-In-One Module
Form No. PS
Page 1 of 5
BIF Doc# 1145
Bussmann
®
Power Module™ Switch
Standard Features:
30-400 amp 600 Vac 3p Fused Power Switch
• 200,000 amp RMS Short-Circuit Current Rating
• Shunt trip 120V
• Control power terminal block
• Ground lug per NEC
• Class J fuse mounting only
1
Optional Features:
Control power transformer with fuses and blocks
Fire safety interface relay
Key to test switch
Pilot light – “ON”
Isolated neutral lug
2
Mechanically interlocked auxiliary contact for hydraulic
elevators with battery backup (5 amp 120 Vac rated)
Fire Alarm Voltage Monitoring Relay (To monitor Shunt Trip
Voltage)
NEMA 3R, 4, and 12 enclosures available
3
Phase failure and undervoltage relay available, consult
factory
For added protection, use the Bussmann SAMI fuse
covers to improve maintenance personnel protection
4
(OSHA 1910.333, paragraph C)
Agency Information:
U.L. 98 Enclosed and Dead Front Switch
Guide 96NK3917, File E182262
NEMA 1, U.L. 50, listed enclosure
cU.L. per Canadian Standards C22.2, No. 0-M91-CAN/CSA
C22.2, No. 4-M89 Enclosed Switch
Power Module™ Switch
Rating (Amps) Power Module Switch Catalog No.
30 PS3
60 PS6
100 PS1
200 PS2
400 PS4
Optional Accessories
1
Catalog
Rating Number
Option 1
Control Power Transformer 208V T20
(CPT) Std. 100VA with PRI & 240V T24
SEC Fuse (120V Secondary) 480V T48
600V T60
Option 2
Fire Safety Interface 24 Vdc Coil R2
Relay (3PDT, 10 amp, 120V) 120 Vac Coil R1
Option 3
Key to Test Switch 120V K
Option 4
Pilot Light – “ON” Red R
Green G
White W
Option 5
Isolated Neutral Lug 30-60A N6
(Full Capacity)
2
100A N1
200A N2
400A N4
Option 6
Mechanically interlocked auxiliary contact 1 NO & 1 NC A
for hydraulic elevators with automatic
recall (5 amp 120 Vac rated)
Option 7
Fire Alarm Voltage Monitoring Relay Single-Pole F1
(To monitor Shunt Trip Voltage) Three-Pole F3
Option 8
Optional Enclosure NEMA 3R U
NEMA 4 Y
NEMA 12 Z
Catalog No. Construction: Catalog number of PS Switch
Options as required in option order as listed above
(i.e. option 1, 2, 3, etc.)
Example: • 100A S.T. Switch 480V-3P – PS1
480–120V CPT – T48
120 Vac Coil Fire Safety Interface Relay – R1
Pilot Light - “ON” (Green) – G
Mech. Interlock (1 NO & 1 NC) – A
Catalog Number PS1T48R1GA
1
Class J fuses not included.
2
Oversized 200% rated neutral option available where required by excessive
non-linear loads.
3
Through 200A.
4
Through 100A.
5
Options 1,2,& 6 are standard for elevator circuits.
Bussmann
®
How to configure Part Numbers:
Step 1: Select Switch Amperage
1
Step 2: Select Options Needed
5
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - Switch PS

8-29-01XXXXXXBussmann®Power Module™Switch PSAll-In-One ModuleForm No. PSPage 1 of 5BIF Doc# 1145Bussmann® Power Module™ SwitchStandard Features:• 30-4

Page 2

Bussmann®Power Module™Switch PSAll-In-One ModuleForm No. PS Page 2 of 5BIF Doc# 1145Standard Shunt Trip RatingsAmp Max Max1Mom

Page 3 - Switch PS

Bussmann®Power Module™Switch PSAll-In-One ModuleForm No. PS Page 3 of 5BIF Doc# 1145Typical Control with Wiring Options for Fire Safety Interface (O

Page 4

Bussmann®Bussmann®Power Module™Switch PSAll-In-One ModuleLegend:N.O.F.A. – Normally Open Fire Alarm contacts supplied from the fire alarm system to

Page 5

Bussmann®Power Module™Switch PSAll-In-One ModuleForm No. PS Page 5 of 5BIF Doc# 1145Section 16XXX – Power Module Switch(Elevator) (Computer Room) (E